Chapter 6 Applied Instruction The PLC receives the data. Additional remark: 1. Please refer to the additional remark on the instruction RS for more information about the related flags and the special registers. 2. The instructions FWD, REV, STOP, RDST, and RSTEF can be used several times in the program, but one instruction is executed at a time. 3. If the value in S exceeds the range, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 4. If D +4 exceeds the device range, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 5. If users declare the operand D in ISPSoft, the data type will be ARRAY [5] of WORD/INT.
6-407 Data Description ‘0’ 16#30 ADR 1 ‘1’ 16#31 ADR 0 ‘0’ 16#30 CMD 1 ‘3’ 16#33 CMD 0 ‘0’ 16#30 Number of data (counted by the byte) ‘A’ 16#41 ‘0’ 16#30 Data in the device at address 16#2100 The PLC automatically converts the ASCII character into the value 16#0000, and 16#0000 is stored in D100. ‘0’ 16#30 ‘0’ 16#30 ‘0’ 16#30 ‘0’ 16#30 Data in the device at address 16#2101 The PLC automatically converts the ASCII character into the value 16#0500, and 16#0500 is stored in D101. ‘5’ 16#35 ‘0’ 16#30 ‘0’ 16#30 ‘0’ 16#33 Data in the device at address 16#2102 The PLC automatically converts the ASCII character into the value 16#01F4, and 16#01F4 is stored in D1072.
‘1’ 16#45 ‘F’ 16#30 ‘4’ 16#30 ‘0’ 16#30 Data in the device at address 16#2103 The PLC automatically converts the ASCII character into the value 16#0000, and 16#0000 is stored in D1073. ‘0’ 16#30 ‘0’ 16#30 ‘0’ 16#30 ‘0’ 16#30 Data in the device at address 16#2104 The PLC automatically converts the ASCII character into the value 16#0000, and 16#0000 is stored in D1074. ‘0’ 16#30 ‘0’ 16#30 ‘0’ 16#30 ‘2’ 16#32 LRC CHK 1 ‘A’ 16#41 LRC CHK 0