AH500 Programming Manual L0 b15 b0 b7 b8 5126 BIN Example 2: Suppose the value in L10 is -3842563 and SM690 is OFF. When the PLC runs, the values in D0, D1, D2, D3, D4, and D5 are 16#202D, 16#2020, 16#3833, 16#3234, 16#3635, and 16#0033 respectively. b15 b0 b7 b8 L10 -384 2563 L11 BIN Additional remark: 1. If D +3 used in the 16-bit instruction exceeds the device range, SM0 is ON, and the error code in SR0 is 16#2003. 2. If D +5 used in the 32-bit instruction exceeds the device range, SM0 is ON, and the error code in SR0 is 16#2003. 3. If the operand D used during the execution of the 16-bit instruction is declared in ISPSoft, the data type will be ARRAY [4] of WORD/INT. 4.
If the operand D used during the execution of the 32-bit instruction is declared in ISPSoft, the data type will be ARRAY [6] of WORD/INT. 6-442 16#20( ) 16#20( ) 16#31(1) 16#35(5) 16#36(6) 16#32(2) 16#00 16#20( ) 16#2D(-) 16#20() 16#20( ) 16#38(8) 16#33(3) 16#32(2) 16#34(4) 16#36(6) 16#35(5) 16#00 16#33(3)