Altivar 16 AC Drive Option card functions, logic and analog output assignment Detection of speed attained Available on: VW3A16201 , VW3A16202 , VW3A16203 . Outputs LO and S2A-S2B. Function Detection of a set level of speed attained by the motor. 3 levels of frequency can be programmed: - Reference speed attained, with VW3A16201 , VW3A16202 or VW3A16203 - Low speed (LSP) attained, with VW3A16201 + VW3A16104 - High speed (HSP) attained, with VW3A16202 , or VW3A16201 + VW3A16104 Use Detection of speed attained is used for a prealarm or alarm. S2A-S2B or LO 1 0 t reference speed t S2A-S2B or LO t 0 1 t 0 LO 1 HSP LSP t Detection of a current level attained Available on: VW3A16201 and VW3A16203 .

Output LO. Function Detection of a current level absorbed by the motor. Two values can be programmed: - Current limit attained, with VW3A16201 option - Overload of 1.1 In attained (In = value of ItH), with options VW3A16201 + VW3A16104 or VW3A16203 . Use Detection of a current level attained can be used for a prealarm or alarm. Detection of 100% thermal state attained Available on: VW3A16201 with or without VW3A16104 . Preset to output LO, can be set to output S2A-S2B. Function Detection of 100% thermal state attained. Use Detection of 100% thermal state attained can be used for a prealarm or alarm. Analog output Available on: VW3A16201 , VW3A16202 , VW3A16203 . Output AO.

Function 0 to 20 mA output signal. Can be set for: - Motor frequency (20 mA = HSP) - Motor current with VW3A16104 (20 mA = 1.82 times the continuous drive output current). 27 f f