Delta Electronics — 1.3.1 Installing a Module

AS Series Module Manual _1 1.3 Installation 1.3.1 Installing a Module 1. Press the clip rings if they are out as the image 1 shown. Push the module to the desire position until you hear a click to finish installation. 2. Link the I/O modules on the right side of the PLC and make sure they are hooked together. Push the modules into the DIN rail until you hear a click. 3. After you installed the module, fasten the screws on the modules to secure the module on the DIN rail.

1-6 Environmental Phenomenon Fast Transient Burst High Energy Surge Radio Frequency Interference Reference Standard IEC 61000-4-4 IEC 61000-4-5 IEC 61000-4-6 Interface/Port Specific Interface/Port Test Level Test Level Test Level Unshielded cable 1 kV 1 kV CM 10 V Digital and analog I/O AC I/O (unshielded) 2 kV 2 kV CM 1 kV DM 10 V Analog or DC I/O (unshielded) 1 kV 1 kV CM 10 V All shielded lines (earth) 1 kV 1 kV CM 10 V Equipment power AC power 2 kV 2 kV CM 1 kV DM 10 V DC power 2 kV 0.5 kV CM 0.5 kV DM 10 V I/O power and auxiliary power output AC I/O and AC auxiliary power 2 kV 2 kV CM 1 kV DM 10 V DC I/O and DC auxiliary power 2 kV 0.5 kV CM 0.5 kV DM 10 V