Chapter 2 Analog Input Module AS04/08AD-A Value of the channel Maximum value 2_ Minimum value Time 7. Records for channels (applicable for AS04AD) Record the input values of the cyclic sampling for each channel. The system saves up to 500 data points and the recording time is 10 ms. Value of the channel 500 records of data Time Instruction for recording Recording ends 8. Scale range You can set the scale range when the format is floating-point. The analog output mode of a channel has a corresponding digital range. Digital values correspond to analog outputs sent by the module.
For example, if the analog range is -10 V to +10 V, the digital range is -10.0 to +10.0, the HSP scale is 10.0, and the LSP scale is -10.0. The digital values -10.0 to +10.0 correspond to the analog values -10 V to +10 V, as the example below shows. 10 V Analog value Rated output range -10 V 10.0 -10.0 Digital value Scale range 2-19