DeviceNet Configuration DeviceNet Configuration NOTE: When emulation mode is enabled, this item is not available. For more details on emulation mode, see Emulation Mode on page 1089. The DeviceNet nodes are scanned using the DeviceNet scanner. For details, see DeviceNet Scan on page 193. After you have scanned the DeviceNet nodes, you can use the information from the scanning process to configure the components in V+. NOTE: The examples presented here are based on the WAGO I/O System 750-306 as a slave on the DeviceNet bus. If you use other DeviceNet equipment, you must ask your DeviceNet vendor for the cor- rect process image of your components.

The following figure shows a typical configuration for the mapping of three digital inputs and one output on the DeviceNet bus to V+ input signals 1033, 1034, and 1035 and V+ output signal 33. The configuration is specific to the WAGO I/O System 750-306 block. The configuration statements are described in detail below. NOTE: The information in the following figure was displayed using the V+ System Configuration editor (see V+ System Configuration Editor on page 221). Sample DeviceNet Configuration for Digital Input and Output To modify the DeviceNet configuration data: 1. Open the Controller object editor 2. Click Configure 3. Select the Configure DeviceNet option 4. Click Next 5.

Click Scan to scan for DeviceNet nodes 6. Select the desired nodes 7. Click Add to add those nodes to the DeviceNet configuration. ACE User's Guide, 3.6.x 18316-000 Rev A Page 216