12. OPERATION 12.1.4 LOAD CONNECTION EG{25B-2 Ay WARNING e Stop the engine and turn the breaker OFF before connecting r A. the load. e Never connect bare cables directly. If bare cables are connected directly, they cannot be tightened sufficiently, and this . will lead to abnormal generation of heat. e Do not connect to the indoor wiring system (the wiring taking electricity from the normal power supply). If the load is connected to the indoor wiring, there is danger that excessive current will flow in the indoor wiring and the generator, and this will cause fire or electric shock. mr Before starting, connect the load cable securely.
When connecting the load cable to output terminal @ and singlephase socket @, do as follows. o/ AE726660 CONNECTING SINGLE-PHASE LOAD When connecting the load for lights, single-phase induction motors, or welding equipment, which use single-phase, do as follows. There are four output terminals: U, V, W, and O. If the load is connected so that the load is balanced and each phase of current has an equal value, the equipment can be used up to the full rating.
When connecting between O - U, O-V, and O- W —-OoO e@ AAT16310 When @ connecting between U - V, V —- W, and W - U AA716320 Voltage Terminal O-W 115/127 (V) Between U -V, V-W, W- U 200/220 (V) Outlet 100/110 (V) Between e@ O-U, O-V, One outlet can be used up to the following capacity. EG125Bs ....... 10 KVA 2-26