Chapter 4 N38143 As a general rule the pressure drop across the grid cooler should be between 14 - 28kPa (2 to 4 psi) this can be acheived by keeping the water velocity below 0.46m/s (5ft/s). The above table shows data that will satisfy all world wide operational conditions. However, if the applica­ tion is known to be only operating in areas where the sea water temperature is unlikely to exceed 25 o C, then when sizing the grid coolers the maximum coolant temperature returning to the intercooler of 43 o C could be used and 75 o C coolant temperatures returning to the engine circuit.

Page 18 Heat rejection data (cont.) Engine model 4.4GM 4.4TGM 4.4TWGM 4.4TW2GM 6TG2AM 6TWGM Heat rejection Jacket water - Engine Btu/min 2440 2838 3338 TBA 5198 6541 kW 42.9 49.9 58.7 TBA 91.4 115 Aftercooler - Intercooler Btu/min - - 77.3 TBA - 1570 kW - - 13.6 TBA - 27.6 Water flow rate, thermostat fully open Engine US gals/min 22-40 20-40 Litres/min 150 150 150 150 77-150 77-150 Intercooler US gals/min - - - - - 20 Litres/min - - 102 102 - 91 Max coolant temp (from grid cooler) Engine oF 140 140 140 140 140 140 oC 60 60 60 60 60 60 Intercooler oF - - 100 100 - 100 oC - - 38 38 - 38