5-101.bk Page 9 Friday, March 17, 2006 11:05 AM 205218 INSPECTION CMCAC Preventive Maintenance 1. Carefully inspect entire system to determine exact location and extent of damage. In case of engine and/or turbocharger failure, perform the following steps to make sure CMCAC system is free from debris: 2. Inspect cold fins and cold bars that run horizontally in cooler. 1. Remove chassis-mounted cooler and flush inside with a safety solvent to remove oil and other foreign debris. 3. Inspect all brazed or welded joints in header tank. 4. Make sure area to be repaired is free of surface oxide and foreign materials such as oil, grease, dirt, etc.
Prior to repair, prepare surface with a clean stainless-steel brush. 2. Shake cooler to remove large pieces. 3. Wash with hot soapy water. Rinse with clean water and blow dry with compressed air in reverse direction of flow. TUNGSTEN-INERT (TIG) WELD METHOD TIG-weld using 1/16–5/32 inch diameter AWS ER 4043 filler rod. Welds should exhibit complete fusion without excessive overlap or undercut. 4. Carefully inspect cooler to ensure cleanliness. Do not use caustic cleaners. MACK recommends pressure-testing the CMCAC system after repairs are complete.
Page 8-9 200 ENGINE INSTALLATION & TESTING Damage Core Failures Recommended Repair Procedure System Check Repairable All header tank-to-core separations All header tank cracks Bent cold fins Tube plate cracks or welds not exceeding 0.25 inch (6.35 mm) in length Tube cracks or weld separations exceeding 0.25 inch (6.35 mm) in length Tungsten-Inert (TIG) weld method Tungsten-Inert (TIG) weld method Straighten with small screwdriver or pair of small needlenose pliers RTV method or Tungsten-Inert (TIG) weld method Tungsten-Inert (TIG) weld method Perform pressure/leak test Perform pressure/leak test Perform pressure/leak test Perform pressure/leak test Perform pressure/leak test Nonrepairable Internal fins damaged and separated from tube plate Tube blockage Cold bar separations or openings exceeding 0.25 inch (6.35 mm) in length Excessive cold fin damage (original shape of fins distorted beyond repair) No repair procedure is recommended — replace unit No repair procedure is recommended — replace unit No repair procedure is recommended — replace unit No repair procedure is recommended — replace unit Perform pressure/leak test Perform pressure/leak test Perform pressure/leak test Perform pressure/leak test