Caterpillar C7 ACERT, C9 ACERT, C11 ACERT, C13 ACERT, C15 ACERT, C18 ACERT, C27 ACERT, C32 ACERT — Caterpillar C7 ACERT, C9 ACERT, C11 ACERT, C13 ACERT, C15 ACERT, C18 ACERT, C27 ACERT, C32 ACERT User Manual (EN)

Peripheral Devices The module is also capable of reading messages, such as warnings, on the J1939 data link and turning a relay, lamp, or alarm on or off depending on the configuration. Many of the messages that the module can recognize are specific to generator set applications but there are a few that would apply to industrial applications. Messages placed on the J1939 data link that can apply to industrial applications are the diagnostic, warning, and/or shutdown messages concerning coolant temperature, coolant level, fuel pressure, fuel filter differential pressure, fuel temperature (C11-C32), oil pressure, intake manifold temperature, and battery voltage.

For example, if the engine ECU sends out a high coolant temperature warning, the discrete I/O module, if configured, can act on that message to energize a relay to open the louvers of an enclosure. The 0 to 120 second delay can also be applied to these conditions. 17.3.2 Discrete Input/Output Module Configuration The discrete I/O module is configured using Cat ET. With the module powered and connected to the CAN data link (see section 17.3.3), the configuration parameters are accessed in the Configuration screen in ET. The Configuration screen lists the 12 discrete inputs and the 8 relay outputs. It also displays the serial number and Instance number of the module.

The Instance number is, in essence, the name of the module. Since there can be multiple modules on the data link, the Instance number can be programmed in order for ET to differentiate between the modules. 17.3.2.1 Configuring the Discrete I/O Module for Use With a Switch on an Input There are four programmable parameters for each of the 12 discrete inputs and two programmable parameters for each of the 8 relay outputs. The four programmable parameters for Discrete Input #1 are: Event Input Function #1 Active State Configuration Event Input Function #1 Event Notification Delay Time Event Input Function #1 Suspect Parameter Number Event Input Function #1 Failure Mode Identifier.

For Discrete Input #2, the parameters are the same except that they are labeled with Event Input Function #2. Discrete input parameters for inputs #3 - #12 are labeled in a similar manner. The input numbers correspond to the connector pin with the same number. For example, Event Input Function #3 would correspond to DIN3, pin 21 on the 40-pin connector. The Active State Configuration parameter has two options, “Low” or “High.” Select “Low” if the desired action by the module takes place when the switch contacts close. Select “High” if the desired action by the module takes place when the switch opens.

The Event Notification Delay Time sets the amount of delay between the time the switch on the input changes states and when the module drives a relay connected to the designated output. The parameter can be programmed from 0 (default) to 120 seconds. There are a number of choices for programming the Suspect Parameter Number and Failure Mode Identifier parameters. The simplest options to use would be “Custom Event” for the Suspect Parameter Number parameter and “Condition Exists” for the Failure Mode Identifier parameter. The two programmable parameters for Relay Output #1 are: Event Output Function #1 Suspect Parameter Number Event Output Function #1 Trigger Condition.

For Event Output Function #2, the parameters are the same except that they are labeled with Event Output Function #2. Relay output parameters for outputs #3 - #8 are labeled in a similar manner. The input numbers correspond to the connector pin with the same number. For example, Event Output Function #3 would correspond to NC_3, C_3, and NO_3, pins 25, 26, and 27 on the 40-pin connector. A P P L I C A T I O N A N D I N S T A L L A T I O N G U I D E 119