Connectors and Wiring Harness Requirements In order that the data bus will function as intended the following requirements must be identified on the customer wire harness print. 1. Remove 75 mm of the outer jacket of data link shielded cable. (Reference Cat part number 153-2707) 2. Remove the foil shield from the exposed wires to within 3 mm of the cable jacket end. 3. Crimp gold-plated socket terminals to the wires and the extended socket terminal to the drain wire. 4. Slide heat shrink tube over the cable end. (Reference Cat part number 125-7876) 5. Install the terminals into the appropriate connector cavity positions. 6. Install the wedge into the connector. 7.

Apply the heat shrink tube over the back of the connector body and the jacket of the cable. The above components and assembly procedures must be used to ensure the cable to connector joint will be sealed. Failure to conform to these requirements will result in cable contamination and result in loss of shield performance. See Figure 6. Figure 6: SAE J1939 Connector Assembly Extended Socket Shrink Tube Wedge Cable Socket Terminals Connector Plug or Receptacle NOTE: Refer to SAE J1939-11 “Physical Layer” document for more information.

5.4.2 Connecting Modules to the CAN Data Link The SAE J1939 data link is used to communicate engine information to an SAE J1939 compatible display or other desired SAE J1939 compatible modules. Refer to SENR9764 “Installation Guide for Industrial Electronic Engine Displays” for more information on connecting J1939 displays to Caterpillar industrial engines. The illustration in Figure 7 shows two J1939 modules properly connected to the J1939 data bus. The key components to note are as follows: • The total length of the data link between terminal resistors must not exceed 40 m (130 ft). • Length of each branch, or stub length, must not exceed 1 m (3.3 ft).

Reference cable assembly (Cat part number 165-0200) that is .15 m long with Deutsch DT 3 pin plug on one end and J1939 signal and shield wires with appropriate crimped socket on the other end for insertion into J1939 module connector. • All splices and end nodes can be implemented using a connector tee. (Reference Deutsch DT receptacle assembly — Cat part number 133-0970). • Two terminal resistors must be installed. One resistor is required at each end of the data link in order to ensure proper operation. These two terminal resistors are critical for the proper operation of the network. (Reference Deutsch DT plug with integrated termination resistor — Cat part number 174-3016).