Engine Speed Demand The Remote Speed Control also provides four lamp drivers that indicate the status of the Remote Speed Control. These drivers can be used to operate lamps or relays and each one is capable of sinking 200mA at 24Vdc. The Remote Active lamp drive is used to indicate that the Remote Speed Control is in Remote Mode. The Local Active driver indicates that the Remote Speed Control is in Local Mode. The Local Hi driver indicates that the Remote Speed Control will not switch modes because the Local Speed is greater than 2.5% higher than the Remote Speed.

The Local Low driver indicates that the Remote Speed Control will not switch modes because the Local Speed is more than 2.5% below the Remote Speed. The 140-2175 Remote Speed Control cannot be used on 12Vdc systems (supply voltage must be between 18Vdc and 32Vdc). 11.3.2 Remote Speed Control Configuration The same three parameters used for the TPS configuration in section 11.1.2 are used for the Remote Speed Control configuration. 1. The Throttle Position Sensor parameter must be programmed to “Installed.” 2. The Throttle Input Low Idle Duty Cycle parameter defaults to 10 and can be set from 10 to 40 (refer to the Remote Speed Control set-up procedure below to determine the proper settings).

3. The Throttle Input High Idle Duty Cycle parameter defaults to 90 and can be set from 50 to 90 (refer to the Remote Speed Control set-up procedure below to determine the proper settings). REMOTE SPEED CONTROL SET-UP PROCEDURE Step 1. Connect the Remote Speed Control to the engine according to the graphic in the Remote Speed Control Installation (Section 11.3.3). Connect Cat ET to the engine. Locate the “Throttle Input Duty Cycle” status parameter in the Cat ET status screens. This parameter is usually on screen 6, but the status screen number can vary depending upon engine model and Cat ET version. Note:

The graphic in section 11.3.3 shows the connections necessary to utilize both the Local Mode and Remote Mode with the ability to switch between the two modes. It is not necessary to include all of the connections shown if only one mode is to be used. For example, if the Local Mode is the only mode to be used then the switch SW1 and the PLC controller are not necessary. If the Remote Mode is the only mode to be used, the 1k potentiometer is unnecessary. Step 2. If the Remote Speed Control is wired for Local Mode use only, skip to Step 6.

If the Remote Speed Control is wired for Remote Mode alone or for the combination of Remote Mode and Local Mode, close switch SW1, grounding the LOCAL/RMTE input. This places the Remote Speed Control into Remote Mode. Step 3. Reduce the PLC output to the minimum current (4mA) and observe the “Throttle Input Duty Cycle” value in Cat ET. Add 5 to this value and record the sum. This sum is the proper value for the “Throttle Input Low Idle Duty Cycle” configuration parameter. Note: This value cannot be less than 10 percent or greater than 40 percent. • Adding 5 provides a tolerance (deadband) for variations in the Remote Speed Control output such as small amounts of temperature-related drift.