Engine Governor Figure 3: Min/Max Engine Speed Governor — Torque vs. Speed Curve Power RSUL RSLL TEL Maximum Throttle LSG HSG Minimum Throttle LI LILL LIUL HILL HIUL HI 600 1800 2100 2300 Engine Speed (RPM) NOTE: PTO Modes and Intermediate Engine Speed are not functional when using the Min/Max Governor (when Engine Governing Primary Mode Configuration is set to Torque Control per Section 13.2.2). At the time of the publication of this manual, ECU software that allows the J1939 Speed Limit Control feature to function with the Min/Max Governor is in the process of being released.

Contact the Application Support Center or Industrial Application and Installation Engineering to determine which ratings have the capability. Top Engine Limit and High Idle Parameters are active when configured to Torque Control. 13.2.2 Min/Max Governor Configuration Two parameters must be configured in Cat ET prior to using the Min/Max Governor. 1. In the configuration screen, Engine Governor Primary Mode Configuration defaults to “Speed Control” and must be set to “Torque Control.” 2. Throttle Position Sensor must be programmed to “installed.” 13.2.3 Min/Max Governor Installation Min/Max Governor requires a Throttle Position Sensor.