MAINTENANCE 2 Check Refrigerant (Gas) Quantity --- every 250 hours 2 WARNING: DO NOT allow liquid refrigerant to contact eye or skin. Liquid refrigerant will freeze eye or skin on contact. Be careful not to loosen connections in the air conditioning circuit. 1 Insufficient refrigerant quantity will reduce cooling capacity of the air conditioner. Check quantity via sight glass (2) provided on receiver tank (1). Inspection Procedure 1. Start the engine and run at approximately 1500 min (rpm). M1JB-07-022 2. Turn the air conditioner switch to ON. 3. Set the blower switch to HI. No Refrigerant Empty 4. Set the temperature control switch to the coolest posi- tion. Almost clear.
A few bub- bles may appear when the engine speed is raised or lowered 5. Check refrigerant quantity through a sight glass on the receiver tank. Sufficient Quantity NOTE: If a sign of oil oozing out of the pipe joint is found, the refrigerant may be leaking. M107-01-010 If the refrigerant level is low, consult your authorized dealer. 3 Check Compressor Belt Tension --- every 250 hours Push (about 98N, 10kgf) Idle Pulley Deflection 6 to 10 mm (0.24 to 0.39 in) Visually check belt for wear. Replace if necessary. Check belt tension by depressing the midpoint between the crank and idle pulleys with the thumb.
Deflection must be 6 to 10 mm (0.24 to 0.39 in.) at a depressing force of approximately 98 N (10 kgf, 22 lbf). Crank Pulley If tension is not within specifications, loosen the bolts for the idle pulley mounting bracket to adjust belt tension. Compressor Pulley NOTE: When a new belt is installed, be sure to re-adjust the tension after operating the engine for 3 to 5 minutes at slow idle speed to be sure that the new belt is seated correctly. M1J1-07-064 7-65