Delta CFP2000 — 2-2 Airflow and Power Dissipation

Chapter 2 Installation  CFP2000 2-2 Airflow and Power Dissipation Table 2-3 2-4 Airflow Rate for Cooling Power Dissipation for AC Motor Drive Model No.

Flow Rate [cfm] Power Dissipation [watt] External Internal Total Loss External Internal Total VFD007FP4EA-41/ 52 / 52S - 14 14 32 20 52 VFD015FP4EA-41/ 52 / 52S - 14 14 43 21 64 VFD022FP4EA-41/ 52 / 52S 34 14 48 74 25 99 VFD037FP4EA-41/ 52 / 52S 34 14 48 92 26 118 VFD040FP4EA-41/ 52 / 52S 34 14 48 113 26 139 VFD055FP4EA-41/ 52 / 52S 34 14 48 139 27 166 VFD075FP4EA-41/ 52 / 52S 34 14 48 195 29 224 VFD110FP4EA-41/ 52 / 52S 88 14 102 240 34 274 VFD150FP4EA-41/ 52 / 52S 88 14 102 309 38 347 VFD185FP4EA-41/ 52 / 52S 88 14 102 353 39 392 VFD220FP4EA-41/ 52 / 52S 88 14 102 449 47 496 VFD300FP4EA-41/ 52 / 52S 200 29 229 618 84 702 VFD370FP4EA-41/ 52 / 52S 200 29 229 726 87 813 VFD450FP4EA-41/ 52 / 52S 285 29 314 864 82 946 VFD550FP4EA-41/ 52 / 52S 285 29 314 1068 84 1152 VFD750FP4EA-41/ 52 / 52S 330 29 359 1407 111 1518 VFD900FP4EA-41/ 52 / 52S 330 29 359 1623 114 1737 ※ The required airflow shown in the table is for installing single drive in a confined space.

※ When installing multiple drives, the required air volume should be the required air volume for single drive X the number of the drives. ※ The heat dissipation shown in the table is for installing single drive in a confined space. ※ When installing multiple drives, volume of heat dissipation should be the heat dissipated for single drive X the number of the drives. ※ Heat dissipation for each model is calculated by rated voltage, current and default carrier.