Delta CFP2000 — 6-2 Specifications of Control Terminal

Chapter 6 Control Terminals  CFP2000 6-2 Specifications of Control Terminal Figure 6-18 Wiring precautions: Table 6-1  In the figure above, the default for STO1, STO2, +24V and SCM1, SCM2, DCM are short circuit. The +24V from section Ⓒ of above figure is for STO only, and cannot be used for other purposes. The default for +24V-COM is short circuit and SINK mode (NPN); please refer to Section 4 Wiring for more detail.  Tighten the wiring with slotted screwdriver: Ⓐ Ⓑ is 3.5 mm (wide) x 0.6 mm (thick); Ⓒ is 2.5 mm (wide) x 0.4 mm (thick)  When wiring bare wires, make sure they are perfectly arranged to go through the wiring holes.

6-7 Terminal Group function Stripping Conductor length [mm] Max. wire gauge Min. wire Torque (±10%) gauge Relay Ⓐ Solid 4–5 Strand 1.5 mm2 [16 AWG] 0.2 mm2 [26 AWG] 5 kg-cm [4.3 lb-in] [0.49 Nm] Control Ⓑ board Solid Strand 6–7 Solid Strand 8 kg-cm [6.9 lb-in] [0.78 Nm] Control Ⓒ board 2 kg-cm [1.7 lb-in] [0.20 Nm] Terminals Termi nal Function Factory Setting (NPN mode) Digital control s +24V (Source) ignal common +24V  5% 200 mA COM Digital control s ignal common (Sink) Common for multi-function input terminals FWD Forward-Stop c FWD-DCM: ommand ON forward running OFF deceleration to stop REV Reverse-Stop c REV-DCM: ommand ON reverse running OFF deceleration to stop