Chapter 6 Control Terminals CFP2000 NOTE: Wire size of analog control signals: 0.75 mm 2 [18 AWG] with shielded wire. Table 6-2 6-9 Terminals Terminal Function Factory Setting (NPN mode) AVI2 Auxiliary analog voltage input Figure 6-21 Impedance: 20 kΩ Range: 0–10 V = 0–Max. Output Frequency (Pr.01-00) DC AFM1 Multi-function analog voltage output Figure 6-22 0–10 V Max. output current 2 mA, Max. load 5 kΩ 0–20 mA Max. load 500 Ω Output current: 20 mA max. Resolution: 0–10 V corresponds to Max. operation frequency Range:
0–10 V 4–20 mA AFM1 / AFM2 Switch, default is 0–10 V AFM2 ACM Analog Signal Common Common for analog terminals STO1 Default setting is shorted Power removal safety function for EN ISO 13849 and IEC 61508 When STO1–SCM1; STO2–SCM2 is activated, the voltage of STO1–SCM1 / STO2–SCM2 must be ≥ 11 V , the internal resistance for STO1–SCM1 / STO2–SCM2 is 3.6 kΩ DC Note: Please refer to Section 18 Safe Torque Off Function. SCM1 STO2 SCM2 SG+ Modbus RS-485 Note: Please refer to Section 12 DESCRIPTION OF PARAMETER SETTINGS group 09 Communication Parameters for more information. SG- SGND RJ45 PIN 1, 2, 7, 8 : Reserved PIN 3, 6: SGND PIN 4: SG- PIN 5: SG+