Delta CFP2000 — 7-2 Magnetic Contactor / Air Circuit Breaker and Non-fuse Circuit Breaker

Chapter 7 Optional Accessories  CFP2000 Non-fuse Circuit Breaker Comply with UL standard: Per UL 508, paragraph 45.8.4, part a. motor drive.

The rated current of the breaker shall be 1.6–2.6 times of the maximum rated input current of AC Table 7-5 7-9 Model Recommended non-fuse breaker [A] VFD007FP4EA-41/-52/-52S 6 VFD015FP4EA-41/-52/-52S 6 VFD022FP4EA-41/-52/-52S 10 VFD037FP4EA-41/-52/-52S 15 VFD040FP4EA-41/-52/-52S 15 VFD055FP4EA-41/-52/-52S 20 VFD075FP4EA-41/-52/-52S 25 VFD110FP4EA-41/-52/-52S 35 VFD150FP4EA-41/-52/-52S 50 VFD185FP4EA-41/-52/-52S 60 VFD220FP4EA-41/-52/-52S 60 VFD300FP4EA-41/-52/-52S 90 VFD370FP4EA-41/-52/-52S 100 VFD450FP4EA-41/-52/-52S 125 VFD550FP4EA-41/-52/-52S 150 VFD750FP4EA-41/-52/-52S 200 VFD900FP4EA-41/-52/-52S 250