5. Applicable Devices and Support Software 5.2. Device Configuration The hardware components to reproduce the connection procedure of this document are as follows. CJ2M-CPU12 + E3NW-ECT + E3NW-DS + Personal computer (CX-One installed, OS:Windows 7) CJ1W-NCF82 E3NX-FA0 E3NX-FA0 Ethernet cable USB cable DS-Bus Precautions for Correct Use The connection line of EtherCAT communication cannot be shared with other Ethernet networks. Make sure to directly connect the PLC to the destination device with the Ethernet cable. Please use the cable (double shielding with aluminum tape and braiding) of Category 5 or higher, and use the shielded connector of Category 5 or higher.
Precautions for Correct Use Update the CX-Programmer to the version specified in this section or higher version using the auto update function. If a version not specified in this section is used, the procedures described in Section 7 and subsequent sections may not be applicable. In that case, use the equivalent procedures described in the CX-Programmer Operation Manual (Cat. No. W466). 4 Manufacturer Name Model Version OMRON Position Control Unit CJ1W-NCF82 Ver.1.3 OMRON CPU Unit CJ2M-CPU12 Ver.2.0 OMRON Power Supply Unit CJ1W-PA202 OMRON CX-One CXONE-AL[][]C-V4 /AL[][]D-V4 Ver.4.[][] OMRON CX-Programmer (Included in CX-One) Ver.9.43 - Personal computer (OS:
Windows7) - - USB cable - OMRON Ethernet cable (with industrial Ethernet connector) XS5W-T421-[]M[]-K OMRON Digital Sensor Communication Unit E3NW-ECT Ver.1.0 OMRON Distributed Sensor Unit E3NW-DS Ver.1.0 OMRON Fiber Amplifier E3NX-FA0 Ver.1.0 - DS-Bus communications cable -