Screen Specifications 22 EIP Status Screen ・ Reads and displays the device information on the IO-Link master unit NXR-ILM08C. ・ Reads and displays the information on Ethernet port connection statuses. ・ Displays logs of FCS errors and outputs to an output variable. 1 2 3 4 5 5 4 12 12 6 11 6 11 7 7 8 8 9 9 10 13 10 13 14 15 16 17 18 19 20 21 No. Part Description 1 DataDisplay IP address of the selected device is displayed. 2 Group Units’ information is shown. Refer to No. 16 and later for details. 3 Button The LED that indicates the location of the IO-Link master unit on the screen is lit when this button is pressed. It is for expansion and not shown in the actual NA.
4 Button Displays connection conditions of ETH1 and ETH2 by any of the following: Undiagnosed, Normally communicating, Short-circuited, Disconnected, Making a diagnosis, Failed to read, or Other error. Default: Undiagnosed 5 Group If ETH1 and/or ETH2 is disconnected, indications that notify a disconnection and a distance to the disconnected point are shown. 6 Button Pressing the Start Logging button begins logging FCS errors. If the number of FCS errors per sampling cycle excesses to a threshold, results are stored to IO variables, LogPort□FCSErrorCount and LogPort□FCSErrorTime. Pressing the Stop Logging button stops logging, but results are not stored.
7 Lamp Displays the progress of logging by any of the following: Logging, Logging paused/Results found, Logging paused/No results, or Abnormal logging termination/No results 8 Button It is for expansion and not shown in the actual NA. 9 Button Clears the value of the array variable in which logs are stored to zero. The integrated value of FCS errors also becomes zero. 10 Button Save logging results to a file. It is for expansion and not shown in the actual NA. 5 5 4 12 6 7 8 9 10 12 13 6 7 8 9 10 14 16 17 18 19 20