Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Using PID Control Setting PID Constants Manually You set the PID constants manually in the Adjustment Level. The default settings of the PID constants are as follows: P (proportional band) = 8.0°C, I (integral time) = 233 seconds, D (derivative time) = 40 seconds. Turn ON the power supply. 1 Operating Display Adjustment Level ← l.adj (L.ADJ) will be displayed to show that the Adjustment Level has been entered. The four numeric digits that identify the product code are displayed. Press the (Level) Key for less than 1 second. Change the parameter with the Key . 2 ← p (P): Indicates the Proportional Band parameter.

← Default setting is 8.0 (8.0°C). Adjustment Level Press the (Mode) Key several times to display p (P). Using PID Control Change the set value with the (Up and Down) Keys. Change the parameter with the Key . 3 Adjustment Level ← i (I): Indicates the Integral Time parameter. Press the (Mode) Key several times to display i (I). ← Default setting is 223 (233 seconds). Change the set value with the Change the parameter with the Key . 4 (Up and Down) Keys. Adjustment Level ← d (D): Indicates the Derivative Time parameter ← Default setting is 40 (40 seconds). Press the (Mode) Key several times to display d (D). Change the set value with the (Up and Down) Keys.

(When finished, press the (Level) Key to return to the operation display.) Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC 3-5