omron — Setting Temperature Alarms

Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Setting Temperature Alarms ⇒ ⇒ ⇒ ⇒ * Refer to the E5CC/E5EC Digital Temperature Controllers User's Manual (Cat. No. H174) for information on alarm types 12 (LBA) to 19 (RSP Absolute-value Lower-limit Alarm). Setting Temperature Alarms 4-4 Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Do you want to link the alarm temperature to the set point? Do you need a standby sequence? In what cases do you want to output an alarm? Alarm Type Operation No. Name Set this number in the Temperature Controller You use these numbers for the following Alarm Type parameters: alt1 (ALT1), alt2 (ALT2), alt3 (ALT3), and alt4 (ALT4).

Refer to page 4-6 for the procedure. 8 Absolute-value Upper-limit Alarm ON ON OFF 0 Temperature Alarm value 9 Absolute-value Lower-limit Alarm ON ON OFF 0 Temperature Alarm value 10 Absolute-value Upper-limit Alarm with Standby Sequence ON ON OFF 0 Temperature Alarm value 11 Absolute-value Lower-limit Alarm with Standby Sequence ON ON OFF 0 Temperature Alarm value ON ON