Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Setting Temperature Alarms Alarm ON Delay and Alarm OFF Delay Alarm ON Delay: You can delay the time when the output actually turns ON from when the alarm status turns ON. Alarm OFF Delay: You can delay the time when the output actually turns OFF from when the alarm status turns OFF. The value is entered in units of seconds. Go to the Advanced Function Setting Level. 1 * For details, refer to the E5CC/E5EC Digital Temperature Controllers User's Manual (Cat. No. H174). Refer to Moving to the Advanced Function Setting Level page 4-14 for the procedure to enter the Advanced Function Setting Level.
Advanced Function Setting Level ← init (INIT) will be displayed to show that the Advanced Function Setting Level has been entered. Change the parameter with the Key . 2 Advanced Function Setting Level a1on (A1ON): ← Indicates the Alarm 1 ON Delay parameter. ← Default setting is 0 (0): Delay disabled. Press the (Mode) Key several times to display a1on (A1ON). Set the parameter with the Keys. 3 Advanced Function Setting Level Change the set value with the (Up and Down) Keys. ← Alarm 1 ON Delay: 10 seconds (example) Setting Temperature Alarms The Alarm OFF Delay parameter follows the Alarm ON Delay parameter.
If required, use the (Mode) Key and the (Up and Down) Keys to repeat steps 2 and 3 and set the ON/OFF delays for a2on (A2ON) (Alarm 2 ON Delay), a3on (A3ON) (Alarm 3 ON Delay), a4on (A4ON) (Alarm 4 ON Delay), a1of (A1OF) (Alarm 1 OFF Delay), a2of (A2OF) (Alarm 2 OFF Delay), a3of (A3OF) (Alarm 3 OFF Delay), and a4of (A4OF) (Alarm 4 OFF Delay). (The number of alarms that is supported depends on the model of Temperature Controller. Some of the alarm parameters may not be displayed.) (When finished, press the (Level) Key for at least 1 second to return to the Initial Setting Level.) 4-13