Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Setting Heater Burnout Alarms 3 Set the heater current to treat as a heater burnout. Set the Heater Burnout Detection 1 parameter in the Adjustment Level to the heater current to treat as a heater burnout. You set this parameter in the Adjustment Level. The parameter is set to 0.0 A by default. Adjustment Level Adjustment Level hb1 (HB1): Indicates the Heater ← Burnout Detection 1 parameter. Heater burnout detection current 1: ← 12.5 A (example) ← Default setting is 0.0 (0.0A). Change the set value with the (Up and Down) Keys. Calculate the heater burnout detection current as follows:
Heater burnout detection current Normal current + Heater burnout current 2 = Example: Using Three 200-V, 1-kW Heaters Connected in Parallel Here, the normal heater current is 15 A, and the heater current for a burnout is 10 A. Heater burnout detection current Normal current 15 A + Heater burnout current = = 25A 2 2 = 25 A/2 = 12.5 A Normal Operation Heater Burnout E5CC/E5EC E5CC/E5EC SSR SSR 15A 1kW 10A 1kW Burnout CT CT 1kW 1kW 1kW 1kW Setting Heater Burnout Alarms 5-2 Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Reference