omron — Setting the Sensor Type

Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC Setting the Sensor Type Setting the Sensor Type You set this parameter in the Initial Setting Level. The parameter is set to 5 (K thermocouple at − 200 to 1,300 °C) by default. 1 Ґ Turn ON the power supply. Operating Display ← If a sensor is not connected or if the setting of the Input Type parameter does not agree w ith the connected sensor, s.err (S.ERR: Input Error) will flash on the display when the power supply is 2 turned ON. If the sensor is not connected, connect it now. Press the Ke y for at least 3 seconds. Press the ( Level) Key for at ← Flashes 3 times. least 3 seconds.

Initial Setting Level ← in-t (IN-T) will be di splayed to show that the Initial Setting Level has been entered. 3 Set the parameter with the Key s. Initial Setting Level ← in-t (IN-T): Indicates the Input Type parameter. ← Default setting is 5 (5): K thermocouple at − 200 to 1,300 °C. Initial Setting Level Change the set value with the ← Input Type: 0 (Pt100 resistance thermometer at (Up and Down) Keys. − 200 to 850 °C) (example) Set the number that you selected for the Input Type parameter on page 1-1. (When finished, press the (Level) Key for at least 1 second to return to the operation display.) Simplicity on the Worksite Solutions Guide for FAQs: E5CC/E5EC 1-2 1 Setting the Sensor Type