Series HMI Connection Manual NOTE 1) Delta HMI can be connected to VLT-2800, 5000, 6000, 7000 controller. 2) Each data length format of Danfoss AC drive parameter is not fixed, therefore, “Multiple Duplicate” function is not provided. 3) Maximum supported alarm number is 16. An alarm number over 16 will result and error. 4) Does not support “optimum read/write” characteristic. 5) If the selected element is a string, the minimum data length should be greater than 2. 6) The default setting for no index No. is 0. 7) The default setting of index No. P606 ~ P617 is 1. 8) Please notice that it is necessary to enter index No. on certain parameters of Danfoss controllers.
Please pay close attention to the setting range of index number. For example, the index No. setting range of the parameter does not starts with 0, if P615 is from 1 to 20, an index value (ex:P615:1) must be entered otherwise read & write failure would occur. For range detail, please see Danfoss manual. 9) CTRWD : Write-only. (Can not be used on the read devices that display the value and input value…etc. It is recommended to be used on the setting value/setting constant (button), or macro function.) 10) STAWD : Read-Only.
11) Control Word V1.00 Revision March, 2010 21 Bit Bit = 0 Bit = 1 15 No Function Reversing 14 Choice of Setup 2 (msb) 13 Choice of Setup 1 (lsb) 12 No Function Relay 04 activated 11 No Function Relay 01 activated 10 Data Not Vaild Vaild 9 Ramp 1 Ramp2 8 Jog 1 OFF ON 7 No Function Reset 6 Ramp Stop Start 5 Hold Ramp Enable 4 Quick-Stop Ramp 3 Coasting Enable 2 DC Brake Ramp 1 Preset reference choice msb 0 Preset reference choice msb