Delta DVP-ES2 — 2.4 SE Memory Map

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming 6. If an SA2/SX2 series MPU is connected to a right-side special module, and M1183 is Off, the range of data registers can be used. Every special module connected to an SA2/SX2 series MPU occupies ten data registers. 7. If an SA2/SX2 series MPU is connected to a left-side special module, and M1182 is Off, the range of data registers can be used. Every special module connected to an SA2/SX2 series MPU occupies ten data registers.

2.4 SE Memory Map 2-8 Specifications Control Method Stored program, cyclic scan system Batch processing method (when END instruction is executed) I/O Processing Method LD instructions – 0.64µs, MOV instructions – 2µs, 1000 steps – approximately 1ms Execution Speed Program language Instruction List + Ladder diagram+ SFC Program Capacity 15872 steps X0~X377, octal number system, 256 points max. Total 480+ points for PLC (*4) X External inputs Y0~Y377, octal number system, 256 points max.

Y External outputs M0~M511, 512 points, (*1) M768~M999, 232 points, (*1) M2000~M2047, 48 points, (*1) Total 4096 points General Auxiliary M M512~M767, 256 points, (*2) M2048~M4095, 2048 points, (*2) relay Latched M1000~M1999, 1000 points, some are latched Special T0~T126, 127 points, (*1) T128~T183, 56 points, (*1) Total 256 points 100ms (M1028=ON, T184~T199 for Subroutines, 16 points, (*1) T64~T126: 10ms) T250~T255(accumulative), 6 points (*1) T Timer 10ms T200~T239, 40 points, (*1) (M1038=ON, T240~T245(accumulative), 6 points, (*1) T200~T245:

1ms) Bit T127, 1 points, (*1) T246~T249(accumulative), 4 points, (*1) Contacts 1ms C0~C111, 112 points, (*1) C128~C199, 72 points, (*1) Total 232 points 16-bit count up C112~C127, 16 points, (*2) 32-bit count C200~C223, 24 points, (*1) up/down C224~C231, 8 points, (*2) C235~C242, 1 phase 1 input, 8 points, (*2) Total 20 points Soft- C Counter ware C233~C234, 2 phase 2 input, 2 points, (*2) 32bit high- C243~C244, 1 phase 1 input, 2 points, (*2) speed count Hard- C245~C248, 1 phase 2 input, 4 points, (*2) up/down ware C251~C254 2 phase 2 input, 4 points, (*2) Initial step point S0~S9, 10 points, (*2) Total 1024 points Step S S10~S19, 10 points (use with IST instruction), (*2) point Zero point return