Delta DVP-ES2 — 2.8 M Relay

DVP-ES2/EX2/SS2/SA2/SX2/SE&TP Operation Manual - Programming Exception: If K is used with an X/Y/M/S device, a nibble device, a byte device, a word device, or a double word device will be formed. Example: K1Y10 represents a device composed of 4 bits, K2Y10 represents a device composed of 8 bits, K3Y10 represents a device composed of 12 bit, and K4Y10 represents a device composed of 16 bits. K1M100 represents a device composed of 4 bits, K2M100 represents a device composed of 8 bits, K3M100 represents a device composed of 12 bit, and K4M100 represents a device composed of 16 bits. Constant (H): A hexadecimal number in a PLC is generally preceded by H.

For example, the hexadecimal number H100 represents the decimal number 256. Reference Table: 2.8 M Relay The types and functions of special auxiliary relays (special M) are listed in the table below. Care should be taken that some devices of the same No. may bear different meanings in different series MPUs. Special M and special D marked with “*” will be further illustrated in 2.13. Columns marked with “R” refers to “read only”, “R/W” refers to “read and write”, “-“ refers to the status remains unchanged and “#” refers to that system will set it up according to the status of the PLC.

2-12 Hexadecimal Binary Octal Decimal (K) BCD (H) (BIN) (OCT) (DEC) (Binary Code Decimal) (HEX) For PLC internal operation No. of X, Y relay Costant K, No. of registers M, S, T, C, D, E, F, P, I devices For DIP Switch and 7- segment display Constant H 0000 0 0 0000 0 0001 1 1 0001 1 0010 2 2 0010 2 0011 3 3 0011 3 0100 4 4 0100 4 0101 5 5 0101 5 0110 6 6 0110 6 0111 7 7 0111 7 1000 10 8 1000 8 1001 11 9 1001 9 1010 12 10 0000 A 1011 13 11 0001 B 1100 14 12 0010 C 1101 15 13 0011 D 1110 16 14 0100 E 1111 17 15 0101 F 10000 20 16 0110 10 10001 21 17 0111 11 SA2 SE OFF STOP RUN Special ES2 Latch Function SS2 SX2    Attrib.

Default M EX2 -ed ON RUN STOP M1000* Monitor normally open contact ○ ○ ○ ○ OFF ON OFF R NO OFF M1001* Monitor normally closed contact ○ ○ ○ ○ ON OFF ON R NO ON M1002* Enable single positive pulse at the moment when RUN is activate (Normally OFF) ○ ○ ○ ○ OFF ON OFF R NO OFF M1003* Enable single negative pulse at the moment when RUN is activate (Normally ON) ○ ○ ○ ○ ON OFF ON R NO ON M1004* ON when syntax errors occur ○ ○ ○ ○ OFF OFF - R NO OFF M1008* Watchdog timer (ON: PLC WDT time out) ○ ○ ○ ○ OFF OFF - R NO OFF M1009 Indicate LV signal due to 24VDC insufficiency ○ ○ ○ ○ OFF - - R NO OFF M1011* 10ms clock pulse, 5ms ON/5ms OFF ○ ○ ○ ○ OFF - - R NO OFF