Chapter 6 Applied Instructions Example 3 The states of the devices are listed below. 6_ *1:Y1 is a dual output. When M0 is OFF, Y1 is controlled by M1. When M0 is ON, Y1 is controlled by M12. 6-153 State of the contact State of the contact during the State of the output coil during the Device before the execution execution of CJ execution of CJ of CJ M0=OFF M0=ON M0=ON Y, M, and S M1, M2, and M3 are OFF. M1, M2, and M3 switch from OFF to ON. Y1*1, M20, and S1 are OFF. M1, M2, and M3 are ON. M1, M2, and M3 switch from ON to OFF. Y1*1, M20, and S1 are ON. Timer M4 is OFF. M4 switches from OFF to ON. The timer is not enabled. M4 is ON.
M4 switches from ON to OFF The timer keeps counting and when the timer setting value is reached, it drives the output T-coil. Accumulative timer M6 is OFF. M6 switches from OFF to ON. ST1 is not enabled. M6 is ON. M6 switches from ON to OFF. The accumulative timer keeps counting and when the timer setting value is reached, it drives the output T-coil. Counter M7 and M10 are OFF. M10 is ON/OFF. The counter is not enabled. M7 is OFF. M10 is ON/OFF. M10 is ON/OFF. C0 stops counting. When M0 switches OFF, C0 keeps counting. Applied instruction M11 is OFF. M11 switches from OFF to ON The applied instruction is not executed. M11 is ON.
M11 switches from ON to OFF The applied instruction is skipped (not executed).