Delta DVP-ES3 — 6.12.2 Explanation of Shift Instructions

DVP-ES3 Series Programming Manual Source n=10 D20 Pointer D0=3 2 1 Additional remarks 1. If the value in D is less than 0, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 2. If D + n -1 exceeds the device range, the instruction is not executed. SM0 is ON, and the error code in SR0 is 16#2003. 3. If n not between 2–512, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#200B. _6 4. You can use the SFWR instruction with the SFRD (API 1105) instruction to write and read the data. 6-318 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0