DVP-ES3 Series Programming Manual 6. If the setting time in S 1 - S 3 is equal to the current time in S , D is OFF, D +1 is ON, and D +2 is OFF. 7. If the setting time in S 1 - S 3 is less than the current time in S , D is OFF, D +1 is OFF, and D +2 is ON. Example 1. When M0 is ON, the instruction compares the setting time 12 hour 20 minute 45 second with the current time in D20 – D22, and stores the comparison result in M10 – M12. When M0 switches from ON to OFF, the instruction is not executed, and the states of M10, M11, and M12 remain the same as they were before M0 switched to ON. 2. If you want to get the comparison result ≧ , ≦ , or ≠, you can connect M10–M12 in series or in parallel.

_6 Additional remarks 1. If S +2 exceeds the device range, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 2. If D +2 exceeds the device range, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 3. If the value in S exceeds the range, an operation error occurs, the instruction is not executed, SM0 is ON, and the error code in SR0 is 16#2003. 6-488