12. Communication Design Examples M0 Sending request M1 M2 M0 Read master frequency and output frequency of AC motor drive and store them in D1050 and D1051 M1 Set the AC motor drive to run forward. D10=H12 M2 Set the master frequency of the drive: 40Hz. D11=K4000 M1127 C0 counts once when data receiving is completed. Reset the flag M1127 M1129 C0 counts once when communication timeout occurs. Reset the flag M1129 M1140 C0 counts once when data receiving error occurs. . Reset the flag M1140. M1141 C0 counts once when parameter error occurs. . Reset the flag M1141 M1000 Send the master frequency of the drive to D0 Send the output frequency of the drive to D1 Program Description: