Delta DVP — 12.11 LINK between PLC, Delta DTA and DTB Temperature Controllers

12. Communication Design Examples Set starting reference for Master to write in DTA: H4701 1 data to be written in DTA Set starting reference for Master to read from DTB: H1000: s 2 data to be read from DTB Set starting reference for Master to write in DTB: H1001 3 data to be written in DTB Auto mode Enable PLC LINK Program Description: z Registers D1480~D1481 in PLC correspond to communication parameters H4700~H4701 of DTA TC. When X0 = ON, PLC LINK will be enabled and the value of H4700~H4701 (present and target temperature) will be shown in D1480~D1481. z Register D1496 in PLC corresponds to communication parameter H4701 of DTA TC.

When X0 = ON, PLC LINK will be enabled and the value of H4701 can be determined by the content in D1496. z Status of DTA TC can be controlled by setting the value in D1496. (D1496 = K300, the target temperature will be 30°C.) z Registers D1512~ D1513 in PLC correspond to communication parameters H1000~H1001 of DTB TC. When X0 = ON, PLC LINK will be enabled and the value of H1000~ H1001 (present and target temperatures) will be shown in D1512~ D1513. z Registers D1528~D1530 in PLC correspond to communication parameters H1001~ H1003 of DTB series temperature controller. When X0 = ON, PLC LINK will be enabled and the value of H1001~ H1003 can be determined by the content in D1528~D1530.

z Target temperature of DTB can be specified by the value in D1528 (D1528 = K400, the target temperature will be 40°C.) z Upper/lower limit of temperature range of DTB can be specified by the value in D1529~1530. (D1529 = K500 and D1530 = K10, the upper limit will be 50°C and lower limit will be 1°C. z Station No. of Slave should be continuous and different from the station No. of Master. SA/SX/SC/SV/EH/EH2 series PLC can be Master. ES/EX/SS series can not be Master. z When X0 = ON, PLC LINK will be enabled. If enabling action is failed, M1350/M1351 will be OFF and X0 needs to be activated again.

DVP-PLC Application Examples 12-40 MOV H4701 MOV K1 MOV H1000 MOV K2 MOV H1001 MOV K3 X0 SET M1351 SET M1350 SET M1350 MOV H4701 MOV K1 MOV H1000 MOV K2 MOV H1001 MOV K3 MOV H4701 D1415 MOV K1 D1450 MOV H1000 D1356 MOV K2 D1435 MOV H1001 D1416 MOV K3 D1451 SET M1351