Delta DVP — 16.1 Ethernet Connection

16. Network Connection Design Examples 16.1 Ethernet Connection PLC_A PLC_B Control Purpose: z Setting up network parameters of DVPEN01-SL directly on the PC (1) IP of PC executing WPLSoft: 192.168.0.3 (2) Subnet mask: 255.255.255.0; Gateway: 192.168.0.1 (3) Set IP of PLC_A: 192.168.0.4; PLC_B: 192.168.0.5 (4) Connect the PC and DVPEN01-SL by RJ-45 cable Note: Both PC and DVPEN01-SL have to adopt static IP. z Writing the time of RTC in PLC_B into D0 ~ D6 of PLC_A (1) Adopting static IP 。 (2) IP of PLC_A: 192.168.0.4 (3) IP of PLC_B: 192.168.0.5 (4) Update form PLC_B to PLC_A Devices:

DVP-PLC Application Examples 16-1 PC Master Ethernet DVPEN01 DVP28SV DVPEN01 DVP28SV DVPEN01 DVP28SV DVPEN01 DVP28SV P OW ER P OWER RS-2 32 RS-2 32 100 M 100 M LIN K L INK R S-232 R S-232 LAN LAN R S LA -232 N R L S-232 AN Device Function M1013 1s clock pulse PLC B M1 _ Write the data into DVPEN01-SL module PLC B M2 _ Check if data exchange is successfully executed.