6 Application Instructions API 00-49 7. “Disable interruption” flags in EH/EH2/SV/EH3/SV2:
DVP-PLC Application Manual 6-13 Flag Function M1280 Disable external interruption I00□ M1281 Disable external interruption I10□ M1282 Disable external interruption I20□ M1283 Disable external interruption I30□ M1284 Disable external interruption I40□ M1285 Disable external interruption I50□ M1286 Disable time interruption I6□□ M1287 Disable time interruption I7□□ M1288 Disable time interruption I8□□ M1289 Disable high-speed counter interruption I010 M1290 Disable high-speed counter interruption I020 M1291 Disable high-speed counter interruption I030 M1292 Disable high-speed counter interruption I040 M1293 Disable high-speed counter interruption I050 M1294 Disable high-speed counter interruption I060 M1295 Disable pulse output interruption I110 M1296 Disable pulse output interruption I120 M1297 Disable pulse output interruption I130 M1298 Disable pulse output interruption I140 M1299 Disable communication interruption I150 M1300 Disable communication interruption I160 M1301 Disable communication interruption I170 M1302 Disable frequency measurement card interruption I180 M1340 Generate interruption I110 after CH0 pulse is sent M1341 Generate interruption I120 after CH1 pulse is sent M1342 Generate interruption I130 when CH0 pulse is being sent M1343 Generate interruption I140 when CH1 pulse is being sent