Mitsubishi — Chapter 6 Application Instructions API 00-49

6 Application Instructions API 00-49 API 26 Operands: S 1 : Source data device 1 S 2 : Source data device 2 D : Operation result Explanations: 1. If S 1 , S 2 and D are used in device F, only 16-bit instruction is applicable. 2. See the specifications of each model for their range of use. 3. This instruction conducts logical AND operation of S 1 and S 2 and stores the result in D . 4. Operation rule: The corresponding bit of the operation result in D will be “0” if any of the bits in S 1 or S 2 is “0”. Program Example 1: When X0 = On, the 16-bit D0 and D2 will perform WAND, logical AND operation, and the result will be stored in D4.

X0 b15 b0 Before execution D0 D2 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 WAND After execution D4 Program Example 2: When X1 = On, the 32-bit (D11, D10) and (D21, D20) will perform DAND, logical AND operation, and the result will be stored in (D41, D40). X1 D40 b15 b0 D11 D10 b31 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 Before execution DAND 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 D21 D20 After execution D41 D40 DVP-PLC Application Manual 6-45 Mnemonic Operands Function W AND P Logical Word AND D Type OP Bit Devices Word Devices Program Steps X Y M S K H KnX KnY KnM KnS T C D E F WAND, WANDP: 7 steps DAND, DANDP:

13 steps S 1 * * * * * * * * * * * S 2 * * * * * * * * * * * D * * * * * * * * 16-bit 32-bit EH3 ES SV2 EH3 SV2 EH3 EX SS S A SX SC EH SV EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV SV2 WAND D0 D2 D4 1 1 1 1 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 1 0 0 1 0 0 0 0 0 0 1 0 0 DAND D10 D20 0 0 0 1 0 0 1 0 0 0 1 1 0 1 0 0 0 0 0 1 0 0 1 0 0 0 1 1 0 1 0 0 0 0 0 1 0 0 1 0 0 0 0 0 0 1 0 0 0 0 0 1 0 0 1 0 0 0 0 0 0 1 0 0