9 Application Instructions API 150-199 Program Example 2: 1. Set the current time in the RTC as 15:27:30, Tuesday, August 19, 2003. 2. D0 ~ D6 indicate the new set time in the RTC. 3. X10 = On for changing the current time in the RTC and make the changed value the new set value. 4. Whenever X11 = On, RTC will perform a ±30 second correction. The correction is performed according to the rules: When the second hand of RTC locates at 1 ~ 29, the second will be automatically reset to “0” and the minute hand will remain at its location. When the second hand locates at 30 ~ 59, the second will be automatically reset to “0” and the minute hand will increase by 1 minute.