2 Functions of Devices in DVP-PLC DVP-PLC Application Manual 2-44 ES SA Off STOP RUN Special EH2 EH3 Function EX SX Attribute Latched Default M SV SV2 SS SC On RUN STOP M1181 Enabling X2 interruption (I201) followed by immediately clearing X0 high-speed counting input value. PS1: Only supports SA/SX V1.8 and versions _ above. PS2: After the high-speed counting value is obtained, the high-speed counting present value will be cleared immediately. ╳ ○ ╳ ╳ Off Off - R/W NO Off M1182 Enabling X3 interruption (I301) followed by immediately clearing X1 high-speed counting input value. PS1: Only supports SA/SX V1.8 and versions _ above. PS2:
After the high-speed counting value is obtained, the high-speed counting present value will be cleared immediately. ╳ ○ ╳ ╳ Off Off - R/W NO Off The default value of M1182 is Off. When M1182 is On, the auto-mapping function is disabled. The analog-to-digital values/digital-to-analog values correspond to D9800~. If the first left-side module connected to EH3-L/SV2 is a communication module, the analog-to-digital values/digital-to-analog values correspond to D9810~. For example, if the modules connected to EH3-L/SV2 from left to right are 04DA-SL and EN01-SL, and M1182 is Off, D9810~D9813 will be assigned to CH1~CH4 in 04DA-SL. ╳ ╳ ╳ ○ On - - R/W NO On M1183 On:
The auto-mapping function of the special module is disabled. PS1: Mapping onto D9900~ PS2: The right side module should support this function.
╳ ╳ ╳ ○ # - - R/W NO # M1184* Enabling modem function (not available in SV) ╳ ╳ ○ ○ Off - - R/W NO Off M1185* Enabling initialization of modem (not available in SV) ╳ ╳ ○ ○ Off - - R/W NO Off M1186* Initialization of modem fails (not available in SV) ╳ ╳ ○ ○ Off - - R/W NO Off M1187* Initialization of modem is completed (not available in SV) ╳ ╳ ○ ○ Off - - R/W NO Off M1188* Displaying whether modem is connecting currently (not available in SV) ╳ ╳ ○ ○ Off - - R/W NO Off M1189 Read/write of Memory card/Flash ROM completed flag (Automatically reset to Off every time when enabled) ╳ ╳ ○ ○ Off - - R/W NO Off M1190 Enabling PLSY for Y0 high-speed output of 0.01 ~ 500Hz ╳ ╳ ○ ○ Off Off - R/W NO Off M1191 Enabling PLSY for Y2 high-speed output of 0.01 ~ 500Hz ╳ ╳ ○ ○ Off Off - R/W NO Off M1192 Enabling PLSY for Y4 high-speed output of 0.01 ~ 500Hz ╳ ╳ ○ ○ Off Off - R/W NO Off M1193 Enabling PLSY for Y6 high-speed output of 0.01 ~ 500Hz ╳ ╳ ○ ○ Off Off - R/W NO Off M1194 I40X, I50X interruptions is able to immediately update the present pulse output value at CH0.
Available in EH2 V1.4 and versions above, _ EH2-L, EH3, and SV2 ╳ ╳ ○ ○ Off Off - R/W NO Off M1195 I40X, I50X interruptions is able to immediately update the present pulse output value at CH1. Available in EH2 V1.4 and versions above, _ EH2-L EH3, and SV2 ╳ ╳ ○ ○ Off Off - R/W NO Off M1196 Setting up the content type in the display (for SX) On: hex; Off: decimal ╳ ○ ╳ ╳ Off - - R/W NO Off M1197 Setting up the display of the 100ths digit (for SX) ╳ ○ ╳ ╳ Off - - R/W NO Off