Mitsubishi — 11.7 Appendix G: Using Ethernet Communication

11 Appendix EtherNet/IP Objects Supported by DVP-SE series PLCs (1) Identity Object (0x01) Instance: 0x01 (2) Message Router ( 0x02 ) Instance: 0x01 (3) Assembly ( 0x04 ) Explicit message Conformance Test is not supported. (4) X input ( 0x64 ) (5) Y output ( 0x65 ) DVP-PLC Application Manual 11-24 Attribute Name Access Data Type Value 0x01 Vendor ID Get UINT 799 (Delta Electronics, inc.) 0x02 Device Type Get UINT 14 (Programmable Logic Controller ) 0x03 Product Code Get UINT 0x0015 0x04 Revision Get STRUCT of:

1.32 Major USINT 0x01 Minor USINT 0x20 0x05 Status Get WORD 0 (Owned ) 0x06 Serial Number Get UDINT 0x07 Product Name Get SHORT STRING _ DVP12SE Attribute Name Access Data Type Value 0x01 Not Support NA NA NA Instance Attribute Name Access Data Type Data 0x65 0x03 D Block 1 Set 10 words D500~D509 0x66 D Block 2 Set 30 words D510~D539 0x67 D Block 3 Set 60 words D540~D599 0x68 D Block 4 Set 100 words D600~D699 0x69 D Block 5 Set 100 words D700~D799 0x6A D Block 6 Set 100 words D800~D899 0x6B D Block 7 Set 100 words D900~D999 Instance Attribute Name Access Data Type 1 0x64 X0 Get BYTE 2 0x64 X1 Get BYTE ……

256 0x64 X377 Get BYTE Instance Attribute Name Access Data Type 1 0x64 Y0 Set BYTE ( 0x00 or 0x01 ) 2 0x64 Y1 Set BYTE ( 0x00 or 0x01 ) …… 256 0x64 Y377 Set BYTE ( 0x00 or 0x01 )