Mitsubishi — 2.10 Special Auxiliary Relays and Special Data Registers

2 Functions of Devices in DVP-PLC DVP-PLC Application Manual 2-49 ES SA Off STOP RUN Special EH2 EH3 Function EX SX    Attribute Latched Default M SV SV2 SS SC On RUN STOP M1353* Enable 32 slave unit linkage and up to 100 data length of data exchange on PLC LINK EH3 V1.2/SV2 V1.0 ╳ ╳ ○ ○ - - - R/W YES Off Others Off - - R/W NO Off M1354* Enable simultaneous data read/write in a polling of PLC LINK EH3 V1.2/SV2 V1.0 ╳ ○ ○ ○ - - - R/W YES Off Others Off - - R/W NO Off M1355 When M1355 = Off, enable PLC LINK for slave connection detection. When M1355 = On, M1360 ~ M1375 (M1440 ~ M1455) will be the flag designating connection, not for slave connection detection.

╳ ○ ○ ○ Off - - R/W YES Off M1356 When the PLC link is enabled and M1356 is ON, the values in D1900~D1931 are taken as the station address. The default station address in D1399 is not used.

╳ ╳ ╳ ○ - - - R/W YES Off M1360* Slave ID#1 status on PLC LINK network ╳ ○ ○ ○ Off - - R YES Off M1361* Slave ID#2 status on PLC LINK network ╳ ○ ○ ○ Off - - R YES Off M1362* Slave ID#3 status on PLC LINK network ╳ ○ ○ ○ Off - - R YES Off M1363* Slave ID#4 status on PLC LINK network ╳ ○ ○ ○ Off - - R YES Off M1364* Slave ID#5 status on PLC LINK network ╳ ○ ○ ○ Off - - R YES Off M1365* Slave ID#6 status on PLC LINK network ╳ ○ ○ ○ Off - - R YES Off M1366* Slave ID#7 status on PLC LINK network ╳ ○ ○ ○ Off - - R YES Off M1367* Slave ID#8 status on PLC LINK network ╳ ○ ○ ○ Off - - R YES Off M1368* Slave ID#9 status on PLC LINK network ╳ ○ ○ ○ Off - - R YES Off M1369* Slave ID#10 status on PLC LINK network ╳ ○ ○ ○ Off - - R YES Off M1370* Slave ID#11 status on PLC LINK network ╳ ○ ○ ○ Off - - R YES Off M1371* Slave ID#12 status on PLC LINK network ╳ ○ ○ ○ Off - - R YES Off M1372* Slave ID#13 status on PLC LINK network ╳ ○ ○ ○ Off - - R YES Off M1373* Slave ID#14 status on PLC LINK network ╳ ○ ○ ○ Off - - R YES Off M1374* Slave ID#15 status on PLC LINK network ╳ ○ ○ ○ Off - - R YES Off M1375* Slave ID#16 status on PLC LINK network ╳ ○ ○ ○ Off - - R YES Off M1376* Indicating Slave ID#1 data transaction status on PLC LINK ╳ ○ ○ ○ Off - - R NO Off M1377* Indicating Slave ID#2 data transaction status on PLC LINK ╳ ○ ○ ○ Off - - R NO Off M1378* Indicating Slave ID#3 data transaction status on PLC LINK ╳ ○ ○ ○ Off - - R NO Off M1379* Indicating Slave ID#4 data transaction status on PLC LINK ╳ ○ ○ ○ Off - - R NO Off M1380* Indicating Slave ID#5 data transaction status on PLC LINK ╳ ○ ○ ○ Off - - R NO Off M1381* Indicating Slave ID#6 data transaction status on PLC LINK ╳ ○ ○ ○ Off - - R NO Off M1382* Indicating Slave ID#7 data transaction status on PLC LINK ╳ ○ ○ ○ Off - - R NO Off M1383* Indicating Slave ID#8 data transaction status on PLC LINK ╳ ○ ○ ○ Off - - R NO Off M1384* Indicating Slave ID#9 data transaction status on PLC LINK ╳ ○ ○ ○ Off - - R NO Off M1385* Indicating Slave ID#10 data transaction status on PLC LINK ╳ ○ ○ ○ Off - - R NO Off M1386* Indicating Slave ID#11 data transaction status on PLC LINK ╳ ○ ○ ○ Off - - R NO Off M1387* Indicating Slave ID#12 data transaction status on PLC LINK ╳ ○ ○ ○ Off - - R NO Off M1388* Indicating Slave ID#13 data transaction status on PLC LINK ╳ ○ ○ ○ Off - - R NO Off M1389* Indicating Slave ID#14 data transaction status on PLC LINK ╳ ○ ○ ○ Off - - R NO Off M1390* Indicating Slave ID#15 data transaction status on PLC LINK ╳ ○ ○ ○ Off - - R NO Off