Mitsubishi — 2.10 Special Auxiliary Relays and Special Data Registers

2 Functions of Devices in DVP-PLC DVP-PLC Application Manual 2-58 ES SA Off STOP RUN EH2 EH3 Special D Function EX SX    Attribute Latched Default SV SV2 SS SC On RUN STOP D1089 ↓ D1099 Process of data for Modbus communication instruction. When the RS-485 communication instruction built-in the PLC is executed, the words of the instruction will be stored in D1089 ~ D1099. You can check whether the instruction is correct by the contents in these registers.

○ ○ ○ ○ 0 - - R NO 0 D1100 Corresponding status after LV signal is enabled ╳ ╳ ○ ○ 0 - - R/W NO 0 D1101* Start address of file registers ╳ ○ ○ ○ - - - R/W YES 0 D1102* Number of data copied in file register ╳ ○ ○ ○ - - - R/W YES 1,600 D1103* Start No. of file register D for storing data (has to be bigger than 2,000) ╳ ○ ○ ○ - - - R/W YES 2,000 D1104* Start No.

of register D for Y0 acceleration/ deceleration pulse output (Not available in SC V1.4 and versions above) ○ ○ ╳ ╳ 0 - - R/W NO 0 D1109* _ COM3 communication protocol setting (for EH2/EH3/SV2) ╳ ╳ ○ ○ H86 - - R/W NO H86 D1110* Average value at analog input channel CH0 in SX/EX or at CH0 on AD card in EH2/EH3/SV2 ○ ○ ○ ○ 0 - - R NO 0 D1111* Average value at analog input channel CH1 in SX/EX or at CH1 on AD card in EH2/EH3/SV2 ○ ○ ○ ○ 0 - - R NO 0 D1112* Average value at analog input channel CH2 in EX ○ ╳ ╳ ╳ 0 - - R NO 0 The low word of the frequency on which CH3 (Y6/Y7) outputs pulses (EH3/SV2 V1.86 and above) ╳ ╳ ╳ V1.86 0 - - R/W NO 0 D1113* Average value at analog input channel CH3 in EX ○ ╳ ╳ ╳ 0 - - R NO 0 The high word of the frequency on which CH3 (Y6/Y7) outputs pulses (EH3/SV2 V1.86 and above) ╳ ╳ ╳ V1.86 0 - - R/W NO 0 D1116* CH0 of analog output in SX/EX CH0 of DA card in EH2/EH3/SV2 ○ ○ ○ ○ 0 0 0 R/W NO 0 D1117* CH1 of analog output in SX/EX CH1 of DA card in EH2/EH3/SV2 ○ ○ ○ ○ 0 0 0 R/W NO 0 D1118* Sampling time of analog/digital conversion in SX/EX/EH2/EH3/SV2 (ms) PS1:

Only when the AD/DA card is in EH2/EH3/SV2 is the function supported.

○ ○ ○ ○ 5 - - R/W NO 5 D1120* COM2 (RS-485) communication protocol ○ ○ ○ ○ H’86 - - R/W NO H’86 D1121 PLC communication address (latched) ○ ○ ○ ○ - - - R/W YES 1 D1122 Remaining number of words of sent data ○ ○ ○ ○ 0 0 - R NO 0 D1123 Remaining number of words of received data ○ ○ ○ ○ 0 0 - R NO 0 D1124 Definition of start word (STX) ○ ○ ○ ○ H’3A - - R/W NO H’3A D1125 Definition of the first end word ○ ○ ○ ○ H’0D - - R/W NO H’0D D1126 Definition of the second end word ○ ○ ○ ○ H’0A - - R/W NO H’0A D1127 Interruption request for receiving specific word in RS instruction (I150) ○ ╳ ╳ ╳ 0 - - R/W NO 0 Number of pulses in the acceleration area of the positioning instruction (Low word) ╳ ╳ ○ ○ 0 - - R NO 0 D1128 Number of pulses in the acceleration area of the positioning instruction (High word) ╳ ╳ ○ ○ 0 - - R NO 0 D1129 Abnormal communication time-out (time:

ms) ○ ○ ○ ○ 0 - - R/W NO 0 D1130 Error code returning from Modbus ○ ○ ○ ○ 0 - - R NO 0 D1131* Low 16 bytes of high-speed counter value extracted by interruption I501 (Not available in SX series PLCs) ╳ ○ ╳ ╳ 0 - - R NO 0 Output/input ratio of CH0 close-loop control (for EH2/SV/EH3/SV2) ╳ ╳ ○ ○ 100 - - R/W NO 100 D1132* High 16 bytes of high-speed counter value extracted by interruption I501 (Not available in SX series PLCs) ╳ ○ ╳ ╳ 0 - - R NO 0 Output/input ratio of CH1 close-loop control (for in EH2/SV/EH3/SV2) ╳ ╳ ○ ○ 100 - - R/W NO 100