Delta — 2.1.3 List of the Control Registers

DVP02TK-S/DVP02TU-S Temperature Control Module Manual _2 2-4 TU CR# TK Attribute Name Description Default Add. (Hex) K16: Pattern 6, 7 setup page for CH2 #11~ #42 -- R/W X According to each setup page Please refer to each setup page.

K0 -- 00B R/W -- Page0 Basic setup page for CH1 -- -- 02B R/W -- Page1 PID setup page for CH1 -- -- 04B R/W -- Page2 Program control setup page for CH1 -- -- 06B R/W O Page3 Pattern 0, 1 setup page for CH1 -- -- 08B R/W O Page4 Pattern 2, 3 setup page for CH1 -- -- 0AB R/W O Page5 Pattern 4, 5 setup page for CH1 -- -- 0CB R/W O Page6 Pattern 6, 7 setup page for CH1 -- -- 0EB R/W O Page10 Basic setup page for CH2 -- -- 10B R/W O Page11 PID setup page for CH2 -- -- 12B R/W O Page12 Program control setup page for CH2 -- -- 14B R/W O Page13 Pattern 0, 1 setup page for CH2 -- -- 16B R/W O Page14 Pattern 2, 3 setup page for CH2 -- -- 18B R/W O Page15 Pattern 4, 5 setup page for CH2 -- -- 1AB R/W O Page16 Pattern 6, 7 setup page for CH2 -- #43 24B X Error code Please refer to error code descriptions.

K0 #45 24D R/W X User-defined 0x0501: Restore to defaults 0x0502: Settings written on flash 0x0504: RS-485 mode and latched (parameter/mode/station number) 0x51CC: Manually export 0x51DD:Auto export (the PID will be invalid after switching to manually export mode.) CR control can be set up by the analog output of DVP02TUL-S/DVP02TKL-S and the digital output of /DVP02TUN-S/DVP02TKR-S/DVP02TKN-S. DVP02TUL-S/DVP02TKL-S: CR#4: CH1 analog output value range K0~K4000 CR#5: CH2 analog output value range K0~K4000 DVP02TUR-S/DVP02TUN-S/DVP02TKR-S/DVP02 TKN-S: CR#4 (bit0/bit1): CH1 digital output Y0/Y1 CR#5 (bit0/bit1):

CH2 digital output Y2/Y3 K0 #46 24E R O CH1 display value The display value is the measured value after being rounded off or the value set to be displayed for the channels. #47 24F R O CH2 display value Symbols: O: Latched. X: Non-latched.