Chapter 2 Control Register 2_ 2-7 TU CR# TK CH1 TK CH2 Attribute Name Description Default Page0 Page10 Add. (Hex) Add. (Hex) #18 012 0F2 R/W O Output 2 control K0: Heating K1: Cooling K2: Alarm Note: not for DVP02TUL-S/ DVP02TKL-S K0 #21 015 0F5 R/W O Output setup K0: cyclic output K1: immediately output DVP02TUN-S/ DVP02TKN-S: K0 (default) DVP02TUR-S/ DVP02TKR-S: K1 (default) Note: not available for DVP02TUL-S/DVP02TKL-S K0/K1 #23 017 0F7 R/W O Output 1: heating/cooling control cycle setup DVP02TUN-S/ DVP02TKN-S: 1~990 at 0.1 per second, default: K10. DVP02TUR-S/ DVP02TKR-S: 30~990 at 0.1 per second (default) Note: not available for DVP02TUL-S/DVP02TKL-S.

K10 /K200 #24 018 0F8 R/W O Output 2: heating/cooling control cycle setup #25 019 0F9 R/W O Alarm 1 output K0~K12, please refer to the error code description. Note: not available for DVP02TUL-S/DVP02TKL-S. K0 #26 01A 0FA R/W O Alarm 2 output K0 #27 01B 0FB R/W O Alarm output 1 upper-limit setup K0 #28 01C 0FC R/W O Alarm output 1 lower-limit setup K0 #29 01D 0FD R/W O Alarm output 2 upper-limit setup K0 #30 01E 0FE R/W O Alarm output 2 lower-limit setup K0 #32 020 100 R/W O PV upper-limit setup for a corresponding output For DVP02TUL-S series When the input value varies, the corresponding output will vary accordingly.

Take 4~20mA as an example, and set the upper-limit to 1000, lower-limit to 0; when the reading is 0, the output will be 4mA K4000 #33 021 101 R/W O PV lower-limit setup for a K0