DVP201/202/211LC-SL Load Cell Module Operation Manual 4-4 CR# Address Attribute Register name Explanation for CH2 (Low word) adjusted #32 H1020 O R/W Digital value given to a point which needs to be adjusted for CH2 (High word) #33 H1021 O R/W Weight of a point which needs to be adjusted for CH1 (Low word) Weight of a weight #34 H1022 O R/W Weight of a point which needs to be adjusted for CH1 (High word) #35 H1023 O R/W Weight of a point which needs to be adjusted for CH2 (Low word) #36 H1024 O R/W Weight of a point which needs to be adjusted for CH2 (High word) #37 H1025 O R/W Maximum which can be measured by CH1 (Low word) Users can specify the maximum weight which can be measured by CH1/CH2.
If a weight measured exceeds the maximum weight, an error code will be stored. #38 H1026 O R/W Maximum which can be measured by CH1 (High word) #39 H1027 O R/W Maximum which can be measured by CH2 (Low word) #40 H1028 O R/W Maximum which can be measured by CH2 (High word) #41 H1029 X R/W Storing all setting values (H’5678) Storing all setting values, and writing them to the flash memory in the load cell module used H0: No action (factory setting) H’FFFF: All setting values are stored successfully. H’5678: Writing all setting values to the flash memory in the load cell module used CR#41: If the value in CR#41 is H’5678, all setting values will be stored in the flash memory.
After the setting values are stored, the value in CR#41 will become H’FFFF. If the value written to CR#41 is not H’5678, it will automatically become H’0. For example, if H1 is written to CR#41, it will become H1. (After the adjustment of points is complete, please use CR#41 to make adjustment parameters retentive.) #42 H102A X R/W Restoring all settings to Restoring all settings to factory settings (H’55AA)