Chapter 1 Introduction Note: In order to meet DIN 1319-1, an error needs to be less than or equal to 0.05% at 20 °C + 10 K. #1: UP and ZP should be connected to a 24 V DC power supply. The current that an output terminal consumes is approximately 1 mA. #2: In an NPN mode, ZP is used. In a PNP mode, UP is used. 1-3 DVP201/202/211LC-SL Load cell module Voltage output Maximum distance for 100 meters connecting a load cell Maximum output current 5 V DC * 300 mA Allowable load 40~4,010 Ω Averaging weights 100 Common-mode rejection ratio ≥100 dB (CMRR @50/60 Hz) Between a digital circuit and the ground: 500 V AC Between an analog circuit and the ground:
500 V AC Between an analog circuit and a digital circuit: 500 V AC Isolation Load cell modules can be connected to the left side of a PLC. The modules connected to a PLC are numbered from 100 to 107 according to the closeness to the PLC. Connecting to a DVP series PLC Operation: 0~55°C (temperature), 5~95% (humidity), pollution degree 2 Storage: -25~70°C (temperature), 5~95% (humidity) Operation/Storage International standards:
IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea) Vibration/Shock resistance DVP211LC-SL Electrical specifications for input Electrical specifications for output terminals terminals Input/Output terminal X0, X1 Y0, Y1, Y2, Y3 Type Digital input Transistor Form DC (sinking or sourcing) -- Specifications Input current: 24 V DC, 5 mA Voltage specifications: 5~30 V DC #1 Input impedance 4.7 KΩ -- Maximum switch frequency 10 kHz 1 kHz Off → On > 15 V DC -- Action level On → Off -- Response Off → On time On → Off Resistive load -- 0.5 A/output (4 A/COM)#2 Maximum Inductive load -- 15 W (30 V DC) load Bulb -- 2.5 W (30 V DC)