Delta — 7.2 Status of DVPDNET-SL

DeviceNet Network Scanner DVPDNET-SL 7 Display of Node Status on Network 7.1 Display of Node Status in Scan List This function is to monitor if DeviceNet slave is offline or not. DVPDNET-SL does read-time monitoring to the nodes in the scan list and maps the status of every node to a bit. You can acquire the node status by monitoring D6032 ~ D6035. See the table below for the corresponding relation between PLC devices and the nodes on the network: When the node in the scan list is normal, the corresponding bit will be off. If the node occurs with abnormality, its corresponding bit will be On. 7.2 Status of DVPDNET-SL You can acquire the real-time status of DVPDNET-SL by monitoring D6036.

When DVPDNET-SL runs normally, D6036 = 0. When DVPDNET-SL is being initialized, the high byte of D6036 = 1 and the low byte = 0. When error occurs in DVPDNET-SL, the high byte of D6036 = 2. For detailed error information, please refer to the error codes, i.e. the low byte of D6036. DVP-PLC Operation Manual 23 PLC Corresponding nodes on the network device b15 b14 b13 … b1 b0 D6032 Node 15 Node 14 Node 13 … Node 1 Node 0 D6033 Node 31 Node 30 Node 29 … Node 17 Node 16 D6034 Node 47 Node 46 Node 45 … Node 33 Node 32 D6035 Node 63 Node 62 Node 61 … Node 49 Node 48 PLC Explanation device b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0 D6036 Status of DVPDNET-SL (0: normal, 1:

initializing, 2: error) Error codes of DVPDNET-SL