DeviceNet Network Scanner DVPDNET-SL 10.2 How to Configure Network by DeviceNet Network Configuration Tool 1) Configuration of DeviceNet slave 1> Open DeviceNet Builder software and select “Setup” => “Communication Setting” => “System Channel”, and the “Serial Port Setting” dialog box will appear as below. 2> Set up the communication parameters in the PC and DVP-SV, e.g. the communication port, address, baud rate and communication format. Click on “OK” after configuration is finished. DVP-PLC Operation Manual 32 VFD-L Set value Explanation parameter 02-00 4 Transmit the frequency of VFD-L via RS485 communication. 02-01 3 Control operation of VFD-L via RS485 communication.
09-00 1 Set the node address of VFD-L in Modbus to 1. 09-01 1 Set the communication rate of VFD-L in Modbus 9600 09-04 1 Set the communication format of VFD-L in Modbus to 7, E, 1, ASCII. Item Function Default COM Port COM port on the PC to be used to communicate with DVP-SV COM1 Address Communication address of DVP-SV 01 Baud rate Communication speed between the PC and DVP-SV 9,600 (bps) Data Bits Communication protocol between the PC and DVP-SV 7 Parity Even Parity Stop Bit 1 Mode Communication mode between the PC and DVP-SV ASCII