Software 4.1.1.7 Programming For programming and testing, connect the programming PC with the appropriate interface as described in chapter 3.7. Requirements Ш PC running MS Windows Ш Programming software KUBES (part no. 680.502.00) installed on the PC Ш Programming cable (part no. 657.151.03) – Connect with the PC’s COM port as specified in KUBES ( а below, Fig. 9) – Connect with the PLC’s programming interface Data transfer rate The transfer format is set to: 9600 bit/s, 8 data bits, 1 start bit, 1 stop bit, odd parity Fig. 9: KUBES interface parameters 42