E808GB — 7.4.3 Track Masks

Kendrion Kuhnke Automation GmbH CAM Creator Pick Control, Options, CAM, Programs from the menu to set the number of cam programs to run on a FIO CAM Control module. A change between programs should occur with reference to the actual speed.  Tick the boxes in the table rows you use.  Set the speeds at which a change of program should occur.  Allocate the programs. The picture below is just an example of the following settings: Row 1: At a speed of 2 or higher, the program changes from 1 to 2. Row 2: At a speed of 5 or higher, the program changes from 2 to 3. If the speed drops to anything between 2 and 5, the program will go back to 2.

Please note that programs can only change in a linear manner, i.e. from 1 to 2 to 3 but not in any other way, i.e. from 1 to 3. 7.4.3 Track Masks To mask tracks You may use a module's digital inputs to disable (mask) any of the tracks. In other words, if the digital inputs "DI" have been allocated appropriately (see first column), the tracks whose boxes are ticked will be actuated by the cam program. Example: In the picture below, all cams will be disabled when DI 0.0 detects a high signal. You must also enable the "Track Masks" mode. See 7.4.4.6 Track Masks.

Kuhnke FIO CAM Control ( E 808 GB ) 37 11/10/2017 NOTE Press Enter to confirm your entries Any change you make to your program sequence table will have to be confirmed by pressing Enter or by moving on to another field. Only then will the Save icon appear. A general recommendation is to press Enter every time you enter a value into the table.