sinee — 6.2 Function Parameter Table

EM500 Open-Loop Vector Control Inverter User Manual 143 F27.13 Soft start incremental 0.00~50.00 %/s 0.60 ● F27.14 feedforward increment 1 0.00~50.00 %/s 0.11 ● F27.15 feedforward increment 2 0.00~50.00 %/s 0.30 ● F27.16 feedforward increment 3 0.00~50.00 %/s 0.75 ● F27.17 feedforward increment 4 0.00~50.00 %/s 1.55 ● F27.18 feedforward increment 5 0.00~50.00 %/s 4.00 ● F27.19 feedforward increment 6 0.00~50.00 %/s 11.00 ● F27.20 Material supply disruptions control way Ones Place:Material supply disruptions detection mode 0: Automatic detection 1: external signal Tens Place:Material supply disruptions detection control 0:

Detect when output is greater than the lower limit of material supply interrupt detection 1: No detection hundreds place: Material supply disruptions process mode 0:Only Error terminal act 1:Parking time delay and Err 2:Material supply disruptions Error 3.Material supply disruption error resumed automatically Thousands place:Brake mode 0:Mode 0 1:Mode 1 Myriad bit: Unwinding reverse mode 0:unrestricted speed 1: Reverse speed limit as per F27.24 11211 〇 F27.21 Material supply disruptions Detection delay 0.0~10.0 s 6.0 ●